Sanyo SAP-K77RAX Manuale Utente

Navigare online o scaricare Manuale Utente per Climatizzatori a split Sanyo SAP-K77RAX. Sanyo SAP-K77RAX User's Manual Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 68
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
TECHNICAL & SERVICE MANUAL
SAP-K77RAX + SAP-C77RAX
SAP-K97RAX + SAP-C97RAX
SAP-K127RAX + SAP-C127RAX
SPLIT SYSTEM AIR CONDITIONER
Indoor Model No.
SAP-K77RAX
SAP-K97RAX
SAP-K127RAX
Indoor Unit
Product Code No.
1 852 350 01
1 852 350 02
1 852 350 03
FILE NO.
Outdoor Model No.
SAP-C77RAX
SAP-C97RAX
SAP-C127RAX
Product Code No.
1 852 350 04
1 852 350 05
1 852 350 06
Outdoor Unit
SAP-K77RAX
SAP-K97RAX
SAP-K127RAX
SAP-C77RAX
SAP-C97RAX
SAP-C127RAX
REFERENCE NO. SM700754
Destination: Russia (50Hz)
Vedere la pagina 0
1 2 3 4 5 6 ... 67 68

Sommario

Pagina 1 - SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUALSAP-K77RAX + SAP-C77RAXSAP-K97RAX + SAP-C97RAXSAP-K127RAX + SAP-C127RAXSPLIT SYSTEM AIR CONDITIONERIndoor Model No.SAP-K

Pagina 2 - Please Read Before Starting

Control PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 3.15ACR-K97GAX1 ... D102 / L637RCS-7S2E-GCross-FlowDC 12VEach Pair of Terminal : 20

Pagina 3 - Table of Contents

Control PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 3.15ACR-K127GAX1 ... D102 / L637RCS-7S2E-GCross-FlowDC 12VEach Pair of Terminal : 2

Pagina 4

Control PCB2-2-2. Outdoor UnitOutdoor Unit SAP-C77RAXDATA SUBJECT TO CHANGE WITHOUT NOTICE.CCBRN - WHT : 213RED (PNK) - WHT : 168Micro FVAC External

Pagina 5 - 1. OPERATING RANGE

Control PCBOutdoor Unit SAP-C97RAXDATA SUBJECT TO CHANGE WITHOUT NOTICE.CCBRN - WHT : 213RED (PNK) - WHT : 168Micro FVAC External Finish Acrylic baked

Pagina 6 - 2. SPECIFICATIONS

Control PCBOutdoor Unit SAP-C127RAXDATA SUBJECT TO CHANGE WITHOUT NOTICE.CCBRN - WHT : 213RED (PNK) - WHT : 168Micro FVAC External Finish Acrylic bake

Pagina 7

2-3. Other Component Specifications5 kohm (at 25 °C)ModelResistancePTN-41G-S6Z< Thermistor (Room sensor) >AC277V 30AModelRatingEL200/240A1-F (

Pagina 8

3. DIMENSIONAL DATAIndoor Unit SAP-K77RAXSAP-K97RAXSAP-K127RAX16

Pagina 9 - 2-2-1. Indoor Unit

Outdoor Unit SAP-C77RAXSAP-C97RAXUnit: mm06066Wide tube service valvedia.9.52(3/8")Narrow tube service valvedia.6.35(1/4")446147824044264296

Pagina 10 - Indoor Unit SAP-K97RAX

Outdoor Unit SAP-C127RAXUnit: mm06066Wide tube service valvedia.12.7(1/2")Narrow tube service valvedia.6.35(1/4")51014782404526429648211370I

Pagina 11 - Indoor Unit SAP-K127RAX

4. REFRIGERANT FLOW DIAGRAM4-1. Refrigerant Flow DiagramIndoor Unit SAP-K77RAXSAP-K97RAXSAP-K127RAXOutdoor Unit SAP-C77RAXSAP-C97RAXSAP-C127RAXInsul

Pagina 12 - 2-2-2. Outdoor Unit

When WiringELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.SP

Pagina 13 - Outdoor Unit SAP-C97RAX

5. PERFORMANCE DATA5-1. Performance chartsIndoor Unit SAP-K77RAXOutdoor Unit SAP-C77RAXIndoor air temperature 27 °C D.B. / 19 °C W.B.Outdoor air tem

Pagina 14 - Outdoor Unit SAP-C127RAX

Indoor Unit SAP-K97RAXOutdoor Unit SAP-C97RAXIndoor inlet airD.B. temp. (°C)98765432125 30 35 40 45 50Outdoor inlet air D.B. temp. (°C)Operating curre

Pagina 15

Indoor Unit SAP-K127RAXOutdoor Unit SAP-C127RAXIndoor inlet airD.B. temp. (°C)< Cooling Characteristics >1110987654325 30 35 40 45 50Outdoor inl

Pagina 16 - 3. DIMENSIONAL DATA

Horizontal distance (m)Axis air velocity (m/s)Vertical distance (m)Room air temp. : 27°CFan speed : HighCooling : Flap angle 0°, : Axis air velocity 0

Pagina 17 - SAP-C97RAX

Horizontal distance (m)Axis air velocity (m/s)Vertical distance (m)Room air temp. : 27°CFan speed : HighCooling : Flap angle 0°, : Axis air velocity 0

Pagina 18

Horizontal distance (m)Axis air velocity (m/s)Vertical distance (m)Room air temp. : 27°CFan speed : HighCooling : Flap angle 0°, : Axis air velocity 0

Pagina 19 - 4. REFRIGERANT FLOW DIAGRAM

5-3. Cooling CapacityIndoor Unit SAP-K77RAXOutdoor Unit SAP-C77RAX230 V Single Phase 50 HzTC : Total Cooling Capacity (kW)SHC : Sensible Heat Capac

Pagina 20 - 5-1. Performance charts

Indoor Unit SAP-K97RAXOutdoor Unit SAP-C97RAX230 V Single Phase 50 HzTC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CM : Compresso

Pagina 21

Indoor Unit SAP-K127RAXOutdoor Unit SAP-C127RAX230 V Single Phase 50 HzTC : Total Cooling Capacity (kW)SHC : Sensible Heat Capacity (kW)CM : Compres

Pagina 22

Fan Motor Compressor6. ELECTRICAL DATA6-1. Electrical CharacteristicsIndoor Unit SAP-K77RAXOutdoor Unit SAP-C77RAXIndoor Unit Outdoor Unit Complete

Pagina 23 - Indoor Unit SAP-K77RAX

Table of Contents1. OPERATING RANGE2. SPECIFICATIONS2-1. Unit Specifications 2-2. Major Component Specifications 2-3. Other Component Specifications

Pagina 24

6-2. Electric Wiring DiagramsIndoor Unit SAP-K77RAXSAP-K97RAXSAP-K127RAXWARNINGTo avoid electrical shock hazard, be sure todisconnect power before ch

Pagina 25

Outdoor Unit SAP-C77RAXSAP-C97RAXSAP-C127RAXWARNINGTo avoid electrical shock hazard, be sure todisconnect power before checking, servicingand/or clean

Pagina 26 - 230 V Single Phase 50 Hz

WARNING7. INSTALLATION INSTRUCTIONS7-1. Installation Site Selection7-1-1. Indoor UnitTo prevent abnormal heat generation and the possibility of fir

Pagina 27

Outdoor unitHot airHeat sourceExhaust fanNO7-1-2. Outdoor UnitFig. 4AVOID:heat sources, exhaust fans, etc. (Fig. 4)damp, humid or uneven locations.Fi

Pagina 28

Cross-Sectional Area (mm2)(A) Power Supply Wiring Length (m)(B) Power Line Length (m)(A) + (B)Fuse orCircuit BreakerCapacity10A3.5514123327C77 / 97C12

Pagina 29

7-3. Remote Control Unit Installation PositionThe remote control unit can be operated from either a non-fixed position or a wall-mounted position.To

Pagina 30 - CONTROLLER

7-4. How to Test Run the Air ConditionerAfter turning on the power of the air conditioner, use the remote controller and follow the steps below to co

Pagina 31 - SAP-C127RAX

7-5. Removing and Installing the GrilleBasically, these models can be installed and wired without removing the grille. If access to any internal part

Pagina 32 - 7. INSTALLATION INSTRUCTIONS

The address can be set in order to prevent interfer-ence between remote controllers when 2 indoor unitsare installed near each other. To set a differe

Pagina 33 - 7-1-2. Outdoor Unit

8. FUNCTIONS8-1. Room Temperature Control(1) CoolingRoom temperature control is obtained by cycling the compressor ON and OFF under control of the r

Pagina 34

9. TROUBLESHOOTING9-1. Check before and after troubleshooting9-2. Air conditioner does not operate.9-3. Some part of air conditioner does not oper

Pagina 35 - 7-3-1. Mounting on a Wall

8-2. Dry Operation (Dehumidification)Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level

Pagina 36 - OPERATION

8-3. Freeze Prevention (Cooling and Dry)This function prevents freezing of the indoor heat exchange coil.When the temperature of the indoor heat exch

Pagina 37

8-4. Automatic Fan Speed (Cooling and Dry)This automatically adjust the indoor fan speed by the difference between the room temperature and set tempe

Pagina 38 - Address Setting mode

9. TROUBLESHOOTING9-1. Check before and after troubleshooting9-1-2. Check inter-unit wiring.Check that inter-unit wiring is correctly connected bet

Pagina 39 - 8. FUNCTIONS

9-2. Air conditioner does not operate.9-2-1. Circuit breaker trips (or fuse blows).(1) When the circuit breaker is set to ON, it is tripped soon. (R

Pagina 40

(2) Circuit breaker trips in several minutes after turning the air conditioner on.There is a possibility of short circuit.Replace with suitableone (la

Pagina 41

(2) Check remote control unit.(3) Check fuse on the indoor P.C.Board.(4) Check TIMER on the remote control unit.YesFirst remote control unit is defect

Pagina 42 - < Cooling >

9-2-3. Only outdoor unit does not run.(1) Check setting temperature.NoIs room temperature too low ?NoCheck to see if inter-unit wiring is correctly c

Pagina 43 - 9-1-3. Check power supply

9-3-1. Only indoor fan does not run.9-3-2. Only flap motor does not run.9-3-3. Only outdoor fan does not run.9-3. Some part of air conditioner doe

Pagina 44

9-3-4. Only compressor does not run.Check compressor motor capacitor.Measure resistance of compressor motor winding.NoYesYesIs overload relay (OLR) w

Pagina 45 - (1) Power is not supplied

1. OPERATING RANGEMaximumMinimum32 °C D.B. / 23 °C W.B.19 °C D.B. / 14 °C W.B.43 °C D.B.19 °C D.B.Temperature Indoor Air Intake Temp. Outdoor Air Int

Pagina 46

9-4-1. Poor cooling.9-4-2. Excessive cooling.NoYesYesYesIf temperature differenceis small, possibility ofgas shortage.NoChange position of remote co

Pagina 47

Insulation testerProbeClipGround wireTerminal plateCoppertube ormetallic partClipInsulation testerProbeFig. 1Fig. 2Fig. 3Fig. 4Coppertube ormetallic p

Pagina 48

FusePCB Ass'yFig. 5Fig. 6Fig. 7Fuse10-2. Checking Continuity of Fuse on PCB Ass'yRemove the PCB Ass'y from the electrical component bo

Pagina 49

INSTRUCTION MANUALSAP-K77GAX + SAP-C77GAXSAP-K97GAX + SAP-C97GAXSAP-K127GAX + SAP-C127GAX(OI-852-6-4181-018-00-1)APPENDIX53

Pagina 50 - 9-4-2. Excessive cooling

2FEATURESThis air conditioner is equipped with cooling, and drying functions. Details on these functions are provided below; refer to these descriptio

Pagina 51 - Resistance

3PRODUCT INFORMATIONIf you have problems or questions concerning your Air Conditioner, you will need the following information. Model and serial numbe

Pagina 52

4NAMES OF PARTSThis illustration is based on the external view of a standard model.Consequently, the shape may differ from that of the air conditioner

Pagina 53 - APPENDIX

5REMOTE CONTROL UNIT (DISPLAY)(1) Operation modeCOOL ...MILD DRY ...FAN ...

Pagina 54 - OI-018-2-EG

6REMOTE CONTROL UNIT CANCELTransmitterWhen you press the buttons on the remote control unit, the mark appears in the display to transmit the setting

Pagina 55 - OI-018-3-EG

7FLAP buttonPress this button either to select the setting of the airflow direction to the auto. flap in each mode or one of the six possible position

Pagina 56 - OI-018-4-EG

2. SPECIFICATIONS2-1. Unit SpecificationsIndoor Unit SAP-K77RAXOutdoor Unit SAP-C77RAXDATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditio

Pagina 57 - OI-018-5-EG

8USING THE REMOTE CONTROL UNITHOW TO INSTALL BATTERIES1. Slide the cover in the direction indicated by the arrow and remove it.2. Install two AAA alka

Pagina 58 - OI-018-6-EG

9OPERATION WITH THE REMOTE CONTROL UNIT1. Operation 2. Adjusting the Fan SpeedA. Automatic fan speedSimply set the FAN SPEED selector button to the

Pagina 59 - OI-018-7-EG

104. ECONOMY ModeECONOMY Mode is used for saving energy.Press the ECONOMY button while operation. The mark appears in the display.To release the ec

Pagina 60 - OI-018-8-EG

11USING THE 12-HOUR ON AND OFF TIMER 1. TIMER ON mode (Example)After the length of time set for TIMER ON elapses, the unit begins operating.The displ

Pagina 61 - OI-018-9-EG

12USING THE 1-HOUR OFF TIMER 1. 1-Hour OFF TimerThis function causes the unit to operate for one hour and then stop, regardless of whether the unit i

Pagina 62 - OI-018-10-EG

13ADJUSTING THE AIRFLOW DIRECTION1. HorizontalThe horizontal airflow can be adjusted by moving the vertical vanes with your hands to the left or right

Pagina 63 - 3. ON/OFF Program Timer

14CARE AND CLEANINGCasing and Grille (Indoor Unit)Clean the casing and grille of the indoor unit with a vacuum cleaner brush, or wipe them with a clea

Pagina 64 - OI-018-12-EG

15TROUBLESHOOTINGIf your air conditioner does not work properly, first check the following points before requesting service. If it still does not work

Pagina 65 - OI-018-13-EG

SANYO Electric co., Ltd.Apr. / 2008R&D center manual

Pagina 66 - OI-018-14-EG

Indoor Unit SAP-K97RAXOutdoor Unit SAP-C97RAXDATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperature 27°C

Pagina 67 - OI-018-15-EG

Indoor Unit SAP-K127RAXOutdoor Unit SAP-C127RAXDATA SUBJECT TO CHANGE WITHOUT NOTICE.Remarks: Rating conditions are:Cooling: Indoor air temperature 27

Pagina 68 - R&D center manual

-Control PCBControl Circuit Fuse ControlsPart No.Microprocessor250V 3.15ACR-K77GAX1 ... D102 / L637RCS-7S2E-GCross-FlowAC MotorIBH-884-066B ... 14BRN-

Commenti su questo manuale

Nessun commento